Micromod RetroPAK: SLC Configuration Manual User Manual
Page 33
Command Series Migration to MOD 30ML
Function Codes – Introduction
The valid actions for CATYPE are:
EOOO
Gain on error, Reset off, Pre-Act off, manual reset off.
OSOO
Gain off, standard Reset, Pre-Act off, manual reset off
PSOO
Gain on process, standard Reset, Pre-Act off, manual reset off.
ESOO
Gain on error, standard Reset, Pre-Act off, manual reset off.
OMOO
Gain off, MICRO-SCAN Reset, Pre-Act off, manual reset off.
PMOO
Gain on process, MICRO-SCAN Reset, Pre-Act off, manual reset off.
EMOO
Gain on error, MICRO-SCAN Reset, Pre-Act off, manual reset off.
EOPO
Gain on error, Reset off, Pre-Act on process, manual reset off
PSPO
Gain on process, standard Reset, Pre-Act on process, manual reset off
ESPO
Gain on error, standard Reset, Pre-Act on process, manual reset off
PMPO
Gain on process, MICRO-SCAN Reset, Pre-Act on process, manual reset off
EMPO
Gain on error, MICRO-SCAN Reset, Pre-Act on process, manual reset off.
EOEO
Gain on error, Reset off, Pre-Act on error, manual reset off
ESEO
Gain on error, standard Reset, Pre-Act on error, manual reset off
EMEO
Gain on error, MICRO-SCAN Reset, Pre-Act on error, manual reset off
EOOE
Gain on error, Reset off, Pre-Act off, manual reset enabled
EOPE
Gain on error, Reset off, Pre-Act on process, manual reset enabled
EOEE
Gain on error, Reset off, Pre-Act on error, manual reset enabled.