Function Code 156 – PID Ratio with Remote SP
reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.
INPUTS - OUTPUTS
Signal Block
Type
Description
S1
PID
Input – S1
Floating Point
Connect to the PID.S1 signal of the
compound. Process Input signal.
S1Q
QUALLOGIC
Output – S1Q
Boolean (Discrete)
Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
Quality
S2
PID
Input – S2
Floating Point
Connect to the PID.S2 signal of the
compound. Remote Setpoint signal.
S3
PID
Input – S3
Floating Point
Connect to the PID.S3 signal of the
compound. Track Reference.
S4
PID
Input – S4
Boolean
Connect to the PID.S4 signal of the
compound. Track Switch.
S5
PID
Input – Floating
Point
Change in the Control tab of the
corresponding PID block. Change the
value for MANUAL RESET – BASE
VALUE.
S6
PID
Input – S6
Floating Point
Feed-forward input for the PID. Enable
in the Options tab of the PID block.
Change the calculation type to Add.
Connect the feed forward input to the
PID.S6 signal of the compound.
S7 N/A
N/A
N/A
S8 N/A
N/A
N/A
S9 N/A
N/A
N/A
S10 N/A
N/A
N/A
S11
PID
Input – S11
Floating Point
Gain Multiplier input for the PID.
Connect to the PID.S11 signal of the
compound or change in the Control tab
of the PID block. Change the value for
GAIN MULTIPLIER INPUT.
S12
ENG
Input – GAIN
Floating Point
Proportional Gain Kp. Enter in the ENG
block. Open the Inputs tab and select
GAIN to change the value.
S13
ENG
Input – RESET
Integral Reset in resets/min (RPM) Ki.
Enter in the ENG block. Open the
156rr - 2