Command Series Migration to MOD 30ML

Function Code 156 – Auto Bias Station

EXPLANATION

Configuration with this compound requires understanding of the compound and how the
PID block is configured in the MOD 30ML/Modcell controllers. Following is the
reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.

INPUTS - OUTPUTS

Signal Block

Type

Description

S1

AUTO BIAS

Input – S1
Floating Point

Connect to the AUTO BIAS.S1 signal
of the compound. Process Input signal.

S1Q

QUALLOGIC

Input – S1
Discrete

Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
quality signal. This signal can force the
controller to Manual mode.

S2 N/A

N/A

N/A

S3

AUTO BIAS

Input – S3
Floating Point

Connect to the AUTO BIAS.S3 signal
of the compound. Track Reference.

S4

AUTO BIAS

Input – S4
Boolean

Connect to the AUTO BIAS.S4 signal
of the compound. Track Switch.

S5

AUTO BIAS

Input – Floating
Point

Change in the Control tab of the PID
(AUTO BIAS) block. Change the value
for MANUAL RESET – BASE
VALUE.

S6

AUTO BIAS

Input – S6
Floating Point

Feed-forward input for the AUTO
BIAS. Enable in the Options tab of the
PID (AUTO BIAS) block. Change the
calculation type to Add. Connect the
feed forward input to the AUTO
BIAS.S6
signal of the compound.

S7 N/A

N/A

N/A

S8 N/A

N/A

N/A

S9

S9 (Exp)

Input – S9
Boolean

Output Increase Inhibit. Connect to the
S9.S9 signal of the compound.

S10

S10 (Exp)

Input – S10
Boolean

Output Decrease Inhibit. Connect to the
S10.S10 signal of the compound

S11

AUTO BIAS

Input – S11
Floating Point

Gain Multiplier input for the AUTO
BIAS. Connect to the AUTO BIAS.S11
signal of the compound or change in the
Control tab of the AUTO BIAS block.
Change the value for GAIN

156ab - 2