Command Series Migration to MOD 30ML
Function Code 156 – Auto Bias Station
EXPLANATION
Configuration with this compound requires understanding of the compound and how the
PID block is configured in the MOD 30ML/Modcell controllers. Following is the
reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.
INPUTS - OUTPUTS
Signal Block
Type
Description
S1
AUTO BIAS
Input – S1
Floating Point
Connect to the AUTO BIAS.S1 signal
of the compound. Process Input signal.
S1Q
QUALLOGIC
Input – S1
Discrete
Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
quality signal. This signal can force the
controller to Manual mode.
S2 N/A
N/A
N/A
S3
AUTO BIAS
Input – S3
Floating Point
Connect to the AUTO BIAS.S3 signal
of the compound. Track Reference.
S4
AUTO BIAS
Input – S4
Boolean
Connect to the AUTO BIAS.S4 signal
of the compound. Track Switch.
S5
AUTO BIAS
Input – Floating
Point
Change in the Control tab of the PID
(AUTO BIAS) block. Change the value
for MANUAL RESET – BASE
VALUE.
S6
AUTO BIAS
Input – S6
Floating Point
Feed-forward input for the AUTO
BIAS. Enable in the Options tab of the
PID (AUTO BIAS) block. Change the
calculation type to Add. Connect the
feed forward input to the AUTO
BIAS.S6 signal of the compound.
S7 N/A
N/A
N/A
S8 N/A
N/A
N/A
S9
S9 (Exp)
Input – S9
Boolean
Output Increase Inhibit. Connect to the
S9.S9 signal of the compound.
S10
S10 (Exp)
Input – S10
Boolean
Output Decrease Inhibit. Connect to the
S10.S10 signal of the compound
S11
AUTO BIAS
Input – S11
Floating Point
Gain Multiplier input for the AUTO
BIAS. Connect to the AUTO BIAS.S11
signal of the compound or change in the
Control tab of the AUTO BIAS block.
Change the value for GAIN
156ab - 2