Pre-configured PID Ratio with Remote SP
S12
ENG
Input – GAIN
Floating Point
Proportional Gain Kp. Enter in the ENG
block. Open the Inputs tab and select
GAIN to change the value.
S13
ENG
Input – RESET
Floating Point
Integral Reset in resets/min (RPM) Ki.
Enter in the ENG block. Open the
Inputs tab and select the input RESET
to change the value.
S14
ENG
Input – PREACT
Floating Point
Derivative rate in minutes Kd. Enter in
the ENG block. Open the Inputs tab and
select the input PREACT to change the
value.
S15
PID
Input – Floating
Point
Derivative Lag constant Ka. Enter the
value in the PID block. Open the
Control tab and change the INPUT
FILTER TPE to PRE-ACT USER and
type the value in the INPUT FILTER
TIME field.
S16
PID
Input – Floating
Point
High Output Limit. Enter the value in
the PID block. Open the Output tab and
change the OUTPUT LIMITS HIGH
field and OUTPUT RANGE HIGH
field.
S17
PID
Input – Floating
Point
Low Output Limit. Enter the value in
the PID block. Open the Output tab and
change the OUTPUT LIMITS LOW
field and OUTPUT RANGE LOW
field.
S18
PID
Input – Count
Algorithm Type. Choose the type in the
PID block. Open the Control tab and
select the value using the
ALGORITHM TYPE drop-down
menu.
S19 N/A
N/A
N/A
S21
PID
Input – Discreet
Controller Action. Choose the action in
the PID block. Open the General tab
and select the desired CONTROLLER
ACTION.
S22 N/A
N/A
N/A
S23 N/A
N/A
N/A
SPTI
PID
Input – Floating
Point
Setpoint track input. Connect to the
PID.SPTI signal of the compound.
P6- 3