Command Series Migration to MOD 30ML

Function Code 10 – High Select

S4

FC10

Input – S4
Floating Point

Connect to the FC10.S4 signal to
the High Selector.

N

FC10

Output – R
Floating Point

Connect from the FC10.N output
signal from the High Selector.

APPLICATIONS

The most common use of function code 10 is to select the highest value. You can also use
this compound for finding the highest value for 2 or 3 inputs by setting a fixed value for
the unused inputs. This value can typically be zero or a negative value that is lower than
the lowest value the connected inputs can assume.

Configuration of the inputs is shown in the next figure:

Figure 10 .2.

High Select
Function Inputs

10 - 2