Micromod RetroPAK: SLC Configuration Manual User Manual

Page 321

background image

Command Series Migration to MOD 30ML

Function Code 156 – PID (Cascade)


To change the value of the Output Limits (S16, S17):

Open the respective PID block and open the Output tab. Change the values for the
Output LimitsLow and High and Output rangeLow and High.

See figure below:

Figure 156c .8.

Function Code
156

Cascade PID

156c - 11