Function Code 2- Manual Set Constant

GENERAL DESCRIPTION

The output of the Manual Set Constant or the Signal Generator is an analog signal
developed within the function that is equal to . This function provides a tunable
output value in engineering units.

UTILIZATION

The MOD 30ML/MODCELL compound FC2 used here has a function block namely the
Expression block.

Figure 2 .1.

FC2 Compound

The Expression block used in this compound has one input named S1 configured as a
floating point. The result of the expression is configured as S1. The data type of the result
is configured as floating point.

This block also allows selection of the data type for the manual set constant compared to
only the analog type in the Bailey Function code 2. There are 10 allowed data types for the
expression block inputs. They are:

Data Type

Allowed Values

Discrete

0 or 1

Short State

0 - 15

Long State

0 - 255

Count

0 - 65535

Date

Year (0 – 99), Month (0 – 12), Day (0 – 31)

Floating Point

IEEE Single precision floating point

2 - 1