beautypg.com

Inputs - outputs, Notes – Micromod RetroPAK: SLC Configuration Manual User Manual

Page 226

background image

Command Series Migration to MOD 30ML

Function Code 8 – Rate Limiter

INPUTS - OUTPUTS

Signal

Block

Type

Description

S1

RATELIM Input – S1

Floating Point

Connect to the RATELIM.S1
signal of the compound. Input to
the rate limiter.

S2

RATELIM Input – S2

LOGIC

Connect to the RATELIM.S2
signal of the compound. Track
enable switch. FALSE – track
enabled, TRUE – track not
enabled. Default value: FALSE

S3

INCLIM

Input – S3
Floating Point

Enter value for the S3 input of
the INCLIM expression block.
Increase rate limit. Default
Value: 1

S4

DECLIM

Input – S4
Floating Point

Enter value for the S4 input of
the DECLIM expression block.
Decrease rate limit Default
Value: 1

N

RATELIM Output – R

Floating Point

Connect from the RATELIM.N
signal of the compound. Output
from the FC7 block is the result
of the calculation.

TIMEDAY ELAPSED Input

TIMEDAY
ms time

Connect from the TIMEDAY
attribute of the IF (Interface)
block to the
ELAPSED.TIMEDAY signal
of the compound. Output from
the FC7 block is the result of the
calculation.

NOTES

Execution Order:

The function blocks in this compound need to be executed in the following order:

ELAPSED

LASTTIME

INCLIM

DECLIM

RATELIM

8 - 2

This manual is related to the following products: