Fc36 - qualified or, General description, Utilization – Micromod RetroPAK: SLC Configuration Manual User Manual
Page 275: Explanation, Function code 36 – qualified or
Function Code 36 – Qualified OR
GENERAL DESCRIPTION
The qualified OR function code monitors the status of up to eight digital inputs and
produces an output signal based upon conditions set by S9 and S10. The output is a logic
1 or 0 and is based upon the number of inputs being less than, equal to, or greater than
the number specified in S9 and the condition set by S10.
UTILIZATION
The MOD 30ML/MODCELL compound FC36 uses an EX block with 10 inputs. S1 thru
S8 are the inputs for the logical OR function.
Function Code 36
EXPLANATION
S9 is an input that is COUNT by data type and specifies the number of inputs that must
equal logic 1. S10 specifies the select inputs.
0 = no. of logic 1 inputs >= S9
1 = no. of logic 1 inputs = S9
36 - 1