Page 364
Command Series Migration to MOD 30ML
Function Code 156 – PID with Manual/Auto Station
EXPLANATION
Configuration with this compound requires understanding of the compound and how the
PID block is configured in the MOD 30ML/Modcell controllers. Following is the
reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.
INPUTS - OUTPUTS
Signal Block
Type
Description
S1
M/A
Input – S1
Floating Point
Connect to the PID.S1 signal of the
compound. Process Input signal.
S1Q
QUALLOGIC Output – S1Q
Boolean
(Discrete)
Connect to the QUALLOGIC.S1Q signal
of the compound. Process Input Quality
S2 N/A
N/A
N/A
S3
M/A
Input – S3
Floating Point
Connect to the PID.S3 signal of the
compound. Track Reference.
S4
M/A
Input – S4
Boolean
Connect to the PID.S4 signal of the
compound. Track Switch.
S5
M/A
Input – Floating
Point
Change in the Control tab of the
corresponding PID block. Change the
value for MANUAL RESET – BASE
VALUE.
S6
M/A
Input – S6
Floating Point
Feed-forward input for the PID. Enable in
the Options tab of the PID block. Change
the calculation type to Add. Connect the
feed forward input to the PID.S6 signal of
the compound.
S7 N/A
N/A
N/A
S8 N/A
N/A
N/A
S9
S9 (Exp)
Input – S9
Boolean
Output Increase Inhibit. Connect to the
S9.S9 signal of the compound.
S10
S10 (Exp)
Input – S10
Boolean
Output Decrease Inhibit. Connect to the
S10.S10 signal of the compound
S11
M/A
Input – S11
Floating Point
Gain Multiplier input for the PID.
Connect to the PID.S11 signal of the
compound or change in the Control tab of
the PID block. Change the value for
GAIN MULTIPLIER INPUT.
156ma - 2