Command Series Migration to MOD 30ML

Pre-configured Single Loop PID with Remote SP

To enable feedforward control and change the feedforward type (S6):

Open the PID block and select the Options tab. See figure below:

Figure P3 .5.

PID with Remote
SP

Connect the desired signal to the feedforward input (PID.S6) of the compound.