beautypg.com

Micromod RetroPAK: SLC Configuration Manual User Manual

Page 299

background image

Command Series Migration to MOD 30ML

Function Code 156 – PID with Local SP

To enable feedforward control and change the feedforward type (S6):

Open the PID block and select the Options tab. See figure below:

Figure 156 .3.

Function Code
156

PID with Local SP

Connect the desired signal to the feedforward input (PID.S6) of the compound.

156 - 5

This manual is related to the following products: