Function Code 3 - Lead / Lag

EXPLANATION

Function code 3 causes the output of the function block to lead or lag changes in the input
signal . The following equation describes the operation:

OUTPUT = OLDOUT +

LEAD * (IN- OLDINP)

(LAG + SCAN)

SCAN * (IN - OLDOUT)

( LAG + SCAN)

+

OUTPUT = OLDOUT +

LEAD * (IN- OLDINP)

(LAG + SCAN)

SCAN * (IN - OLDOUT)

( LAG + SCAN)

+

This is programmed in to the LEAD/LAG expression block as below:

Y = YL +

S3 * ( S1 - S1L)

S4 + DT

+

DT * (S1 - YL)

S4 + DT

Y = YL +

S3 * ( S1 - S1L)

S4 + DT

+

DT * (S1 - YL)

S4 + DT

INPUTS - OUTPUTS

Signal

Type

Block

Description

S1

Input – S1
Floating Point

FC3

Connect to the FC3.S1 signal of the
compound. Input to the Lead/Lag function.

Input – S1L
Floating Point

LEAD/LAG Value of the last input (input of the previous

cycle)

Input – S3
Floating Point

Time Constant T1 (Lead) in seconds

Input – S4
Floating Point

Time Constant T2 (Lag) in seconds

Input – Y
Floating Point

Present Output value

Input – YL
Floating Point

Value of the last output (output of the
previous cycle)

Input – DT
Floating Point

Scan (Module cycle time) in seconds

N

Output – R
Floating Point

LEAD/LAG Connect from the LEAD/LAG.N signal of

the compound. Output from the LEAD/LAG
block is the result of the lead / lag calculation.