Page 149
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
S10 N/A
N/A
N/A
S11
PID
Input – S11
Floating Point
Gain Multiplier input for the PID.
Connect to the PID.S11 signal of the
compound or change in the Control tab
of the PID block. Change the value for
GAIN MULTIPLIER INPUT.
S12
ENG
Input – GAIN
Floating Point
Proportional Gain Kp. Enter in the ENG
block. Open the Inputs tab and select
GAIN to change the value.
S13
ENG
Input – RESET
Floating Point
Integral Reset in resets/min (RPM) Ki.
Enter in the ENG block. Open the
Inputs tab and select the input RESET
to change the value.
S14
ENG
Input – PREACT
Floating Point
Derivative rate in minutes Kd. Enter in
the ENG block. Open the Inputs tab and
select the input PREACT to change the
value.
S15
PID
Input – Floating
Point
Derivative Lag constant Ka. Enter the
value in the PID block. Open the
Control tab and change the INPUT
FILTER TPE to PRE-ACT USER and
type the value in the INPUT FILTER
TIME field.
S16
PID
Input – Floating
Point
High Output Limit. Enter the value in
the PID block. Open the Output tab and
change the OUTPUT LIMITS HIGH
field and OUTPUT RANGE HIGH
field.
S17
PID
Input – Floating
Point
Low Output Limit. Enter the value in
the PID block. Open the Output tab and
change the OUTPUT LIMITS LOW
field and OUTPUT RANGE LOW
field.
S18
PID
Input – Count
Algorithm Type. Choose the type in the
PID block. Open the Control tab and
select the value using the
ALGORITHM TYPE drop-down
menu.
S19 N/A
N/A
N/A
P4- 3