Single Loop Process Controller Instruction Manual

Single Loop (PID) Controller 61

5.3.1 Abbreviated Configuration Tables

Table 5-1

through

Table 5-8

are provided as a quick reference source for the contiguration datapoints.

These tables do not have the definition column; therefore, for the initial instrument configuration,

Section 4

should be referenced until each datapoint functionality can be recognized by its title. These tables are pro-
vided because even though the functionality of the datapoints can eventually be recognized by title, the
specific datapoint locations can not always be remembered.

Table 5-2. Analog lnput (ANI) Module

Title

Symbol

ANI0

Datapoint

ANI1

Datapoint

Default

Analog Input
(Display Only)

ANI

H000

H001

0

Engineering
Span

SPAN

C256

C257

100

Engineering
Zero

ZERO

C276

C277

0

Digital Filter
Index

DFILT

B269

B270

3

0-5 V lnput

NOBIAS

L416

L417

0

Square Root
Signal

SQRT

L440

L441

0

Calibrate Zero

CIZ

B263

B264

Calibrate Span

CIS

C296

C297

Tag Name

AITAG

A224

A225

ANI0
ANI1

Engineering
Units

AIEU

A298

A299

Percent

Table 5-3. Analog Output (ANO) Module

Title

Symbol

ANO0

Datapoint

Default

Analog Output
(Display Only)

ANO

C000

0

0 - 210 mA
Output

OZBASE

L472

0

Calibrate Zero

COZ

B267

Calibrate Span

COS

C300

Tag Name

AOTAG

A244

ANO0