Single Loop Process Controller Instruction Manual

48 Configuration Parameters

Table 4-7. Contact Output Module (CCO)

Title

Symbol

CCO0

Datapoint

Default

Attribute

Purpose: This module allows the action of the CCO to be reversed (normally a closed contact =1, but
can be changed to = 0).

Contact Output
(Display Only)

CCO

L024

0

If CCO = 0 and OINV = 0, then it is open.
If CCO = 0 and OINV = 1, then it is closed.
If CCO = 1 and OINV = 0, then it is closed.
If CCO = 1 and OINV = 1, then it is open.

Contact Output
Invert

OINV

L288

0

As shown above, it reverses the action of the
CCO datapoint.

Tag Name

COTAG

A280

CCO0

It is an assignable 10 character name for the
contact control output.