104 Easy-Tune

11.3 EASY-TUNE Parameters

All pertinent input parameters to the EASY-TUNE algorithm are obtained from Controller Module Mode 0,
which must first be configured. The parameters that must be configured before initiating the EASY-TUNE
sequence (B008 = 1) are items 1, 3, 5 through 10, in

Table 11-1

.

Table 11-1. EASY-TUNE Parameters

Item

Datapoints

Description

Default

Value

1

L520

C385
C386
C387
C388
C389
C390

Enable Tuning Parameter Limits
0 - no limits checked, 1 - limits below apply
lowest % PB
highest % PB
lowest TR (minutes)
highest TR (minutes)
lowest TD (minutes)
highest TD (minutes)

1

2

500

0

30

0

10

2

L521

Abort EASY-TUNE Switch
0 - no effect, 1 - EASY-TUNE is aborted

0

3

L522

Automatic Tuning Parameter
1 - upon successful completion of the EASY-TUNE sequence,
new tuning parameters will be entered.
0 - new tuning parameters will not be entered but available for review.

0

4

B008

Enable EASY-TUNE

0

5

B385

Control Module Selector (leave at 0)

0

6

B386

PID Control Mode
1 - P, 2 - PI, 3 - PID, 4 - PD, 5 - I

0

7

C378

Excursion Limit for Preliminary Step Disturbance (%)
The step size chosen for C381 will cause a PV change which depends
on the process gain as well as C381 itself. C378 should be set to
approximately 1/4 of that expected change. (See C381 below.)

2

8

C379

Limiting Settling Time (seconds)
Set to maximum time allowed during B387 = 1 or 2. (See

Table 11-2

and

Figure 11-1

.)

0

9

C380

Maximum Allowable Excursion of PV in EASY-TUNE (%)
Setting C380 will prevent excessive change in PV.

0

10

C381

Step Size Change in Controller Output (± %)
Set large enough to cause significant but allowable PV changes.
(See C378 above.)

0