Single Loop Process Controller Instruction Manual
104 Easy-Tune
11.3 EASY-TUNE Parameters
All pertinent input parameters to the EASY-TUNE algorithm are obtained from Controller Module Mode 0,
which must first be configured. The parameters that must be configured before initiating the EASY-TUNE
sequence (B008 = 1) are items 1, 3, 5 through 10, in
Table 11-1. EASY-TUNE Parameters
Item
Datapoints
Description
Default
Value
1
L520
C385
C386
C387
C388
C389
C390
Enable Tuning Parameter Limits
0 - no limits checked, 1 - limits below apply
lowest % PB
highest % PB
lowest TR (minutes)
highest TR (minutes)
lowest TD (minutes)
highest TD (minutes)
1
2
500
0
30
0
10
2
L521
Abort EASY-TUNE Switch
0 - no effect, 1 - EASY-TUNE is aborted
0
3
L522
Automatic Tuning Parameter
1 - upon successful completion of the EASY-TUNE sequence,
new tuning parameters will be entered.
0 - new tuning parameters will not be entered but available for review.
0
4
B008
Enable EASY-TUNE
0
5
B385
Control Module Selector (leave at 0)
0
6
B386
PID Control Mode
1 - P, 2 - PI, 3 - PID, 4 - PD, 5 - I
0
7
C378
Excursion Limit for Preliminary Step Disturbance (%)
The step size chosen for C381 will cause a PV change which depends
on the process gain as well as C381 itself. C378 should be set to
approximately 1/4 of that expected change. (See C381 below.)
2
8
C379
Limiting Settling Time (seconds)
Set to maximum time allowed during B387 = 1 or 2. (See
and
.)
0
9
C380
Maximum Allowable Excursion of PV in EASY-TUNE (%)
Setting C380 will prevent excessive change in PV.
0
10
C381
Step Size Change in Controller Output (± %)
Set large enough to cause significant but allowable PV changes.
(See C378 above.)
0