beautypg.com

Table c-2. database (continued) – Micromod Micro-DCI: 53SL5100A Single Loop Controller User Manual

Page 145

background image

Single Loop Process Controller Instruction Manual

Database 137

Control
Alarm Mode

AIX

B335

1

This parameter defines the Alarm Active (PA1 & PA2)
interpretation of the two Alarm Limits (PL1 & PL2). It is
entered into the datapoint as an index value (0-6) as
follows:
0 PA1: High when PV > PL1
PA2: Low when PV < PL2
1 - None
2 PA1: High when PV > PL1
PA2: not affected
3 PA1: not affected
PA2: Low when PV < PL1
4 PA1: High when PV > PL1
PA2: Hi-Hi when PV > PL2
5 PA1: Low when PV < PL1
PA2: Lo-Lo when PV < PL2
6 PA1: Hi-Dev when Dev > PL1
PA2: Lo-Dev when Dev < PL2

Alarm Examples:

B335 PV PL1 PL2 Alarm Setpoint Notes
(C103) (C104)

0 >60 60 HIGH Alarm Limit 1 is set for 60. If PV exceeds 60 = HIGH alarm.

0 <40 40 LOW Alarm Limit 2 is set for 40. If PV falls below 40 = LOW alarm.

2 >60 60 HIGH Alarm Limit 1 is set for 60. If PV exceeds 60 = HIGH alarm.

2 <40 40 N/A Alarm Limit 2 is set fo 40. If PV falls below 40 = no alarm condition.

3 >60 60 N/A Alarm Limit 1 is set for 60. It PV exceeds 60 = no alarm condition.

3 <40 40 LOW Alarm Limit 2 is set for 40. If PV falls below 40 = LOW alarm.

4 >60 60 HIGH Alarm Limit 1 is set for 60. If PV exceeds 60 = HIGH alarm.

4 >70 70 HI-HI Alarm Limit 2 is set for 70. If PV exceeds 70 = HI-HI alarm.

5 <40 40 LOW Alarm Limit 1 is set for 40. If PV falls below 40 = LOW alarm.

5 <30 30 LO-LO Alarm Limit 2 is set for 30. If PV falls below 30 = LO-LO alarm.

6 >50 10 HI-DEV 40 Alarm Limit 1 = 10, Setpoint at 40. If PV exceeds 50 = HI-DEV alarm.

6 <30 -10 LO-DEV 40 Alarm Limit 2 = -10, Setpoint at 40. If PV falls below 30 = LO-DEV alarm.

Analog
Output
(Display
Only)

ANO0

C000

0

The value in this datapoint represents the percent of
output to be generated by hardware (e.g., 100 % output =
20 mA).

Process
Variable

PV

C100

0

This is the actual PV variable of the controller PID
algorithm. It is obtained from ANI0.

Setpoint

SP

C101

0

This is the actual setpoint of the PID algorithm obtained
from the setpoint increase/decrease pushbuttons or from
Remote Setpoint (RSP).

Table C-2. Database (Continued)

Title

Symbol Datapoint

Default

Attribute