Single Loop Process Controller Instruction Manual

Configuration Parameters 53

No Byte
Stuffing

CB

L2581

0

When set to a 1, this datapoint disables the
standard MicroMod communication protocol feature
which inserts a 00 (NUL) byte after every 7EH
(SOH) that is not the beginning of a message. (This
permits user-written communications software to
determine the number of bytes to expect in a
response message.) It must be set to 0 when using
MicroMod communications software or equipment.

Datalink
Disable

DLD

L257

0

When set to 0, it permits full Datalink
communication capabilities. When set to 1, it
disables Datalink communication capabilities.

Table 4-11. System Module

Title

Symbol

System

Module

Datapoint

Default

Attribute

Purpose: Purpose: The primary purpose of this module is to select and initiate the instrument mode of
operation, and set the Scan Index.

Function Index

FIX

B00

0

The operational algorithm of the unit is selected
by the value of this parameter:
0 = Suspend mode. No control algorithm
execution. The logo is displayed.
1 = CS1, Single Loop PID Controller operation
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ratio Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around the
display perimeter remains lit.
98 = Defaults database then sets FIX to 0.

Display Brightness
Index

BRIGHT

B12

4

This parameter controls the display screen
intensity. A value of 0 is the brightest and a value
of 7 is the dimmest intensity. Normal viewing
setting is 4.

EASY-TUNE
Enable

ETE

B08

0

When set to a 1, the EASY-TUNE algorithm is
implemented. This parameter is left at 0 for
normal instrument operation. (See

Section 11

for

EASY-TUNE.)

Unit Tag Name

TAG

A08

SL5100

This is an assignable 10 character name for the
system module (SL5100).

Table 4-10. Communication Module (Continued)

Title

Symbol

CCO0

Datapoint

Default

Attribute