Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 99
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 99 of 126
GF-129
Ph.: 800-526-0288
11/06/2014
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
15
05-Fire Rate In
boilerload_15
AV:25
data
float
25
nvoBlrLoad15
inc count (9)
Output (non-polled)
30018/15
15
06-Outlet Temp
localsuptemp_1
5
AV:26
data
float
26
nvoLocSupTmp15
inc count (9)
Output (non-polled)
30003/15
15
07-Display Code
dispcode_15
AV:27
data
float
27
nvoDispCode15
inc count (9)
Output (non-polled)
30001/15
15
08-Unit Status
unitstat_15
AV:28
data
float
28
nvoUnitStat15
inc count (9)
Output (non-polled)
30002/15
15
09-Run Cycles
runcycles_15
AV:29
data
float
29
nvoRunCycles15
51
Output (non-polled)
30012-30013/15
15
10-Run Hours
runhours_15
AV:30
data
float
30
nvoRunHours15
51
Output (non-polled)
30014-30015/15
C-More Addr 16
16
01-Fire Rate Out
boilerstate_16
AV:31
data
float
31
nvoBlrState16
inc count (9)
Output (non-polled)
30009/16
16
02-Active Setpoint
effectsetpt_16
AV:32
data
float
32
nvoEffSetpt16
inc count (9)
Output (non-polled)
30017/16
16
03-Net Remote
Setpt
setpt_16
AV:33
data
float
33
nviSetpt16
inc count (9)
Input (non-polling)
40001/16
16
05-Fire Rate In
boilerload_16
AV:35
data
float
35
nvoBlrLoad16
inc count (9)
Output (non-polled)
30018/16
16
06-Outlet Temp
localsuptemp_16
AV:36
data
float
36
nvoLocSupTmp16
inc count (9)
Output (non-polled)
30003/16
16
07-Display Code
dispcode_16
AV:37
data
float
37
nvoDispCode16
inc count (9)
Output (non-polled)
30001/16
16
08-Unit Status
unitstat_16
AV:38
data
float
38
nvoUnitStat16
inc count (9)
Output (non-polled)
30002/16
16
09-Run Cycles
runcycles_16
AV:39
data
float
39
nvoRunCycles16
51
Output (non-polled)
30012-
30013/16
16
10-Run Hours
runhours_16
AV:40
data
float
40
nvoRunHours16
51
Output (non-polled)
30014-
30015/16
E Valve Addr 17
17
01-Cntl Output
Signal
boilerstate_17
AV:171
data
float
171
nvoEcsState17
inc count (9)
Output (non-polled)
30004/17