Table C-2: Eight C-Mores and One ACS/BMS II/BMS

Equip

Point Name

Name

Read

Only

BACnet

Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon Direction

ModBus/

Unit Address

128

24-Net Blr 7 Status

blr15stat_13

AV:12

data

float

144 nvoNetBlr7Stat

inc count (9)

Output (non-polled)

30032/128

128

25-Net Blr 8 Status

blr16stat_13

AV:13

data

float

145 nvoNetBlr8Stat

inc count (9)

Output (non-polled)

30033/128

128

26-Return Temp

localrettemp_13

AV:173

data

float

173

nvoLocRetTmp

inc count (9)

Output (non-polled)

30004/128