beautypg.com

3 set ip address for bacnet/ip and modbus tcp, Set ip address for bacnet/ip and modbus tcp, Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 30

background image

AERCO ProtoNode Gateway

User Manual

Page 30 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

5.3 Set IP Address for BACnet/IP and Modbus TCP

• Open a PC web browser, enter the default IP address of the ProtoNode 192.168.1.24

and connect to the ProtoNode.

• From the GUI main landing, click on Diagnostics and Debugging to get to the Utilities

section of the GUI (to change IP Address and other capabilities). (Figure 5-3)

Figure 5-3: Changing IP Address using Main Landing Page for ProtoNode

• From the GUI’s Utility page, click on setup and then Network Settings to enter the Edit

IP Address Settings menu.

• Modify the IP address (N1 IP address field) of the ProtoNode Ethernet port.

• If necessary, change the Netmask (N1 Netmask field).

• Type in a new Subnet Mask

• If necessary, change the IP Gateway (Default Gateway field)

• Type in a new IP Gateway

• Note: If the ProtoNode is connected to a router, the IP Gateway of the ProtoNode

should be set to the IP address of the router that it is connected to

• Reset ProtoNode by selecting “System Restart” or cycling the power.

• Unplug Ethernet cable from PC and connect it to the network hub or router