Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 75

AERCO ProtoNode Gateway
User Manual
OMM-0080_0H
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 75 of 126
GF-129
Ph.: 800-526-0288
11/06/2014
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/U
nit Address
2
05-Fire Rate In
boilerload_2
AV:50
data
float
15
nvoBlrLoad2
inc count (9)
Output (non-polled)
30018/2
2
06-Outlet Temp
localsuptemp_2
AV:51
data
float
16
nvoLocSupTmp2
inc count (9)
Output (non-polled)
30003/2
2
07-Display Code
dispcode_2
AV:52
data
float
17
nvoDispCode2
inc count (9)
Output (non-polled)
30001/2
2
08-Unit Status
unitstat_2
AV:53
data
float
18
nvoUnitStat2
inc count (9)
Output (non-polled)
30002/2
2
09-Run Cycles
runcycles_2
AV:44
data
float
19
nvoRunCycles2
51
Output (non-polled)
30012-
30013/2
2
10-Run Hours
runhours_2
AV:45
data
float
20
nvoRunHours2
51
Output (non-polled)
30014-
30015/2
2
11-Oxygen
o2level_2
AV:162
data
float
162 nvoO2Lev2
inc count (9)
Output (non-polled)
30010/2
2
12-Exhaust Temp exhtemp_2
AV:182
data
float
182 nvoExhTmp2
inc count (9)
Output (non-polled)
30007/2
Blr Addr 3
3
01-Fire Rate Out
boilerstate_3
AV:54
data
float
21
nvoBlrState3
inc count (9)
Output (non-polled)
30009/3
3
02-Active
Setpoint
effectsetpt_3
AV:55
data
float
22
nvoEffSetpt3
inc count (9)
Output (non-polled)
30017/3
3
03-Net Remote
Setpt
setpt_3
AV:56
data
float
23
nviSetpt3
inc count (9)
Input (non-polling)
40001/3
3
05-Fire Rate In
boilerload_3
AV:60
data
float
25
nvoBlrLoad3
inc count (9)
Output (non-polled)
30018/3
3
06-Outlet Temp
localsuptemp_3
AV:61
data
float
26
nvoLocSupTmp3
inc count (9)
Output (non-polled)
30003/3
3
07-Display Code
dispcode_3
AV:62
data
float
27
nvoDispCode3
inc count (9)
Output (non-polled)
30001/3