Appendix F.3: BCM Fault Code Table

The table below lists the fault codes and troubleshooting tips associated with the BCM.

Table F-3: BCM Fault Code Table

Code

Description

Effect

Correction

Reset

17

Boiler Pipe is frozen.
FlowSensor temp. is
36°F or less.

Ignition is
inhibited. Pump
runs for 5 min
at max speed.

Carefully defrost boiler

AUTOMATIC - when
FlowSensor is greater
than 41°F.

18

Maximum Δ-
temperature
protection. Flow
temperature - Return
Temperature > Water

Δ-Temp Protection +
50°F

All burners
turned OFF
and Pump ON
at maximum
speed.

Check the system
installation.

AUTOMATIC - when

Δ-temperature <

Water Δ-Temp
Protection.

19

High outlet
temperature.
FlowSensor
temperature > 203°F.

All burners
turned OFF
and Pump ON
at maximum
speed.

Check Flow Sensor or
system pump

AUTOMATIC - when
FlowSensor < 176°F.

37

Crash

Ignition is
inhibited

Change the BCM

MANUAL – push
reset switch to cycle
power

38

Settings Corrupted

Ignition is
inhibited. Pump
runs for 5 min
at max speed.

Re-program the settings.
Contact Factory

MANUAL - push reset
switch or cycle
power.

50

Internal Failure

Ignition is
inhibited.

Contact Factory for new
BCM.

MANUAL - cycle the
power.

56

Standby. No remote
control detected and
Request input is open.

Ignition is
inhibited.

Close Request input for
Manual operation.

MANUAL - push reset
switch or cycle
power.

57

No BMM detected.

Ignition is not
possible.

Check the BMM eBus
wiring.

MANUAL - push reset
switch or cycle
power.

58

FlowSensor fault.

All burners
turned OFF.

Check flow sensor or
wiring.

AUTOMATIC