Table C-5: ECS and SmartPlate
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon
SNVT
Lon Direction
ModBus/Unit
Address
31
01-Cntl Output Signal
boilerstate_3
AV:9
data float
15
nvoEcsState31
inc count (9)
Output (non-polled)
30004/31
31
02-Setpoint
effectsetpt_3
AV:150
data float
16
nvoEcsSetpt31
inc count (9)
Output (non-polled)
30006/31
31
03-RmSetpt
rmsetpt_3
AV:151
data float
17
nviEcsSetptRq31
inc count (9)
Input (non-polling)
40027/31
31
04-Outlet Temp
localsuptemp_3
AV:152
data float
18
nvoEcsSupTmp31
inc count (9)
Output (non-polled)
30002/31
31
05-FBk Sensor Temp
localrettemp_3
AV:153
data float
19
nvoEcsRetTmp31
inc count (9)
Output (non-polled)
30290/31
31
06-Over Temp Alarm
unitstat_3
AV:154
data float
20
nvoEcsStat31
inc count (9)
Output (non-polled)
30075/31
31
07-Flow Rate
flowrate_3
AV:155
data float
21
nvoEcsFlow31
inc count (9)
Output (non-polled)
30291/31
E Valve Addr 32
32
01-Cntl Output Signal
boilerstate_4
AV:10
data float
22
nvoEcsState32
inc count (9)
Output (non-polled)
30004/32
32
02-Setpoint
effectsetpt_4
AV:158
data float
23
nvoEcsSetpt32
inc count (9)
Output (non-polled)
30006/32
32
03-RmSetpt
rmsetpt_4
AV:159
data float
24
nviEcsSetptRq32
inc count (9)
Input (non-polling)
40027/32
32
04-Outlet Temp
localsuptemp_4
AV:160
data float
25
nvoEcsSupTmp32
inc count (9)
Output (non-polled)
30002/32
32
05-FBk Sensor Temp
localrettemp_4
AV:161
data float
26
nvoEcsRetTmp32
inc count (9)
Output (non-polled)
30290/32
32
06-Over Temp Alarm
unitstat_4
AV:156
data float
27
nvoEcsStat32
inc count (9)
Output (non-polled)
30075/32
32
07-Flow Rate
flowrate_4
AV:157
data float
28
nvoEcsFlow32
inc count (9)
Output (non-polled)
30291/32