Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 79
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 79 of 126
GF-129
Ph.: 800-526-0288
11/06/2014
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/U
nit Address
7
10-Run Hours
runhours_7
AV:99
data
float
70
nvoRunHours7
51
Output (non-polled)
30014-
30015/7
7
11-Oxygen
o2level_7
AV:167
data
float
167 nvoO2Lev7
inc count (9)
Output (non-polled)
30010/7
7
12-Exhaust Temp exhtemp_7
AV:187
data
float
187 nvoExhTmp7
inc count (9)
Output (non-polled)
30007/7
Blr Addr 8
8
01-Fire Rate Out
boilerstate_8
AV:110
data
float
71
nvoBlrState8
inc count (9)
Output (non-polled)
30009/8
8
02-Active
Setpoint
effectsetpt_8
AV:111
data
float
72
nvoEffSetpt8
inc count (9)
Output (non-polled)
30017/8
8
03-Net Remote
Setpt
setpt_8
AV:112
data
float
73
nviSetpt8
inc count (9)
Input (non-polling)
40001/8
8
05-Fire Rate In
boilerload_8
AV:104
data
float
75
nvoBlrLoad8
inc count (9)
Output (non-polled)
30018/8
8
06-Outlet Temp
localsuptemp_8
AV:105
data
float
76
nvoLocSupTmp8
inc count (9)
Output (non-polled)
30003/8
8
07-Display Code
dispcode_8
AV:106
data
float
77
nvoDispCode8
inc count (9)
Output (non-polled)
30001/8
8
08-Unit Status
unitstat_8
AV:107
data
float
78
nvoUnitStat8
inc count (9)
Output (non-polled)
30002/8
8
09-Run Cycles
runcycles_8
AV:108
data
float
79
nvoRunCycles8
51
Output (non-polled)
30012-
30013/8
8
10-Run Hours
runhours_8
AV:109
data
float
80
nvoRunHours8
51
Output (non-polled)
30014-
30015/8
8
11-Oxygen
o2level_8
AV:168
data
float
168 nvoO2Lev8
inc count (9)
Output (non-polled)
30010/8
8
12-Exhaust Temp exhtemp_8
AV:188
data
float
188 nvoExhTmp8
inc count (9)
Output (non-polled)
30007/8
Blr Addr 9
9
01-Fire Rate Out
boilerstate_9
AV:120
data
float
81
nvoBlrState9
inc count (9)
Output (non-polled)
30009/9