Appendix C.6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
Mlx Addr 1
1
01-Act Mod Lev
boilerstate_1
AV:121
data
float
121
nvoMlxState1
inc count (9)
Output (non-polled)
41009/1
1
02-Target Setpoint
effectsetpt_1
AV:122
data
float
122
nvoMlxSetpt1
inc count (9)
Output (non-polled)
41019/1
1
03-Req Outlet
Temp
setpt_1
AV:123
data
float
123
nviMlxSetptRq1
inc count (9)
Input (non-polling)
41005/1
1
04-Net Direct Drive
boilercmd_1
AV:124
data
float
124
nviMlxCmd1
inc count (9)
Input (non-polling)
40002/1
1
05-Mod Lev In
boilerload_1
AV:125
data
float
125
nvoMlxLoad1
inc count (9)
Output (non-polled)
41201/1
1
06-Flow Sens
Temp
localsuptemp_1
AV:126
data
float
126
nvoMlxSupTmp1
inc count (9)
Output (non-polled)
41003/1
1
07-Display Code
dispcode_1
AV:127
data
float
127
nvoMlxDispCode1
inc count (9)
Output (non-polled)
30001/1
1
11-Error Code
errcode_1
AV:128
data
float
128
nvoMlxErrCode1
51
Output (non-polled)
40001/1
1
08-Unit Status
unitstat_1
AV:129
data
float
129
nvoMlxStat1
inc count (9)
Output (non-polled)
30002/1
1
09-Ret Flow Temp
returntemp_1
AV:130
data
float
130
nvoMlxRetTmp1
inc count (9)
Output (non-polled)
41004/1
Mlx Addr 2
2
01-Act Mod Lev
boilerstate_2
AV:131
data
float
131
nvoMlxState2
inc count (9)
Output (non-polled)
41009/
2
02-Target Setpoint
effectsetpt_2
AV:132
data
float
132
nvoMlxSetpt2
inc count (9)
Output (non-polled)
41019/2
2
03-Req Outlet
Temp
setpt_2
AV:133
data
float
133
nviMlxSetptRq2
inc count (9)
Input (non-polling)
41005/2
2
04-Net Direct Drive
boilercmd_2
AV:134
data
float
134
nviMlxCmd2
inc count (9)
Input (non-polling)
40002/2
2
05-Mod Lev In
boilerload_2
AV:135
data
float
135
nvoMlxLoad2
inc count (9)
Output (non-polled)
41201/2