Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2 Type

N2

ID

Lon SNVT

NAME

Lon

SNVT

Lon Direction

ModBus
Address

5

Unit Type

SMD_BAS_IP_HTR_05_[11]

AV:711

Data Float

137

nvoHTR_05_12 inc count (9)

Output (non-polled)

30711

5

Unit Size

SMD_BAS_IP_HTR_05_[12]

AV:712

Data Float

138

nvoHTR_05_13 inc count (9)

Output (non-polled)

30712

5

Value State

SMD_BAS_IP_HTR_05_[13]

AV:713

Data Float

139

nvoHTR_05_14 inc count (9)

Output (non-polled)

30713

5

Net Remote Setpt

SMD_BAS_IP_HTR_05_[14]

AV:714

Data Float

140

nvoHTR_05_15 inc count (9)

Output (non-polled)

30714

5

Run Cycles Upper

SMD_BAS_IP_HTR_05_[15]

AV:715

Data Float

141

nvoHTR_05_16 inc count (9)

Output (non-polled)

30715

5

Run Cycles Lower

SMD_BAS_IP_HTR_05_[16]

AV:716

Data Float

142

nvoHTR_05_17 inc count (9)

Output (non-polled)

30716

5

Run Hours Upper

SMD_BAS_IP_HTR_05_[17]

AV:717

Data Float

143

nvoHTR_05_18 inc count (9)

Output (non-polled)

30717

5

Run Hours Lower

SMD_BAS_IP_HTR_05_[18]

AV:718

Data Float

144

nvoHTR_05_19 inc count (9)

Output (non-polled)

30718

5

Oxygen Level

SMD_BAS_IP_HTR_05_[19]

AV:719

Data Float

145

nvoHTR_05_20 inc count (9)

Output (non-polled)

30719

Blr Addr 6

6

Comm Address

SMD_BAS_IP_HTR_06_[0]

AV:800

Data Float

146

nvoHTR_06_1

inc count (9)

Output (non-polled)

30800

6

Unit Status

SMD_BAS_IP_HTR_06_[1]

AV:801

Data Float

147

nvoHTR_06_2

inc count (9)

Output (non-polled)

30801

6

Fault Code

SMD_BAS_IP_HTR_06_[2]

AV:802

Data Float

148

nvoHTR_06_3

inc count (9)

Output (non-polled)

30802

6

Outlet Temp

SMD_BAS_IP_HTR_06_[3]

AV:803

Data Float

149

nvoHTR_06_4

inc count (9)

Output (non-polled)

30803

6

FFWD Temp

SMD_BAS_IP_HTR_06_[4]

AV:804

Data Float

150

nvoHTR_06_5

inc count (9)

Output (non-polled)

30804

6

Inlet Temp

SMD_BAS_IP_HTR_06_[5]

AV:805

Data Float

151

nvoHTR_06_6

inc count (9)

Output (non-polled)

30805

6

Exhaust Temp

SMD_BAS_IP_HTR_06_[6]

AV:806

Data Float

152

nvoHTR_06_7

inc count (9)

Output (non-polled)

30806

6

Air Temp

SMD_BAS_IP_HTR_06_[7]

AV:807

Data Float

153

nvoHTR_06_8

inc count (9)

Output (non-polled)

30807

6

Flame Strength

SMD_BAS_IP_HTR_06_[8]

AV:808

Data Float

154

nvoHTR_06_9

inc count (9)

Output (non-polled)

30808

6

Fire Rate In

SMD_BAS_IP_HTR_06_[9]

AV:809

Data Float

155

nvoHTR_06_10

inc count (9)

Output (non-polled)

30809

6

Fire Rate Out

SMD_BAS_IP_HTR_06_[10]

AV:810

Data Float

156

nvoHTR_06_11

inc count (9)

Output (non-polled)

30810

6

Unit Type

SMD_BAS_IP_HTR_06_[11]

AV:811

Data Float

157

nvoHTR_06_12

inc count (9)

Output (non-polled)

30811

6

Unit Size

SMD_BAS_IP_HTR_06_[12]

AV:812

Data Float

158

nvoHTR_06_13 inc count (9)

Output (non-polled)

30812

6

Value State

SMD_BAS_IP_HTR_06_[13]

AV:813

Data Float

159

nvoHTR_06_14 inc count (9)

Output (non-polled)

30813

6

Net Remote Setpt

SMD_BAS_IP_HTR_06_[14]

AV:814

Data Float

160

nvoHTR_06_15 inc count (9)

Output (non-polled)

30814