Appendix B.1: AERCO C-More & ACS/BMS II/BMS Point Definitions (Cont.)
Point Name
BAS Modbus
Data Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus
Data
Address
(Hex/Dec.)
Units (Range)
ACS/BMS II/BMS (Cont.)
06-Display Code
30011
Fault/Message
Code
Input
0x000A / 10
Bit (0 to 65535)
Bit 0 = Outside Air Sensor
Error
Bit 1 = Header Sensor Error
Bit 2 = Interlock 1 Error
Bit 3 = Interlock 2 Error
Bit 4 = Indoor Air/Return
Sens Error
Bit 5 = 4-20 mA Input Error
07-Num Boilers Fired
30008
Total Boilers
Fired
Input
0x0007 / 7
(0 to 40) BMS
(0 to 32) BMSII
08-Num Boilers Online
30009
Total Boilers On
Line
Input
0x0008 / 8
(0 to 40) BMS
(0 to 32) BMSII
09-Last Blr Fired
30017
Last Boiler Fired
Input
0x0010 / 16
(1 to 40) BMS
(1 to 32) BMSII
10-Boiler 1 Status
30018
Boiler 1 Status
(PWM Boiler 1)
Input
0x0011 / 17
Enum (1 to 40, 119, 120)
1 to 40 = Fired and Sequence
119 = Not On Line
120 = On Line But Not Fired
11-Boiler 2 Status
30019
Boiler 2 Status
(PWM Boiler 2)
Input
0x0012 / 18
Same As Above
12-Boiler 3 Status
30020
Boiler 3 Status
(PWM Boiler 3)
Input
0x0013 / 19
Same As Above
13-Boiler 4 Status
30021
Boiler 4 Status
(PWM Boiler 4)
Input
0x0014 / 20
Same As Above
14-Boiler 5 Status
30022
Boiler 5 Status
(PWM Boiler 5)
Input
0x0015 / 21
Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
15-Boiler 6 Status
30023
Boiler 6 Status
(PWM Boiler 6)
Input
0x0016 / 22
Same As Above
16-Boiler 7 Status
30024
Boiler 7 Status
(PWM Boiler 7)
Input
0x0017 / 23
Same As Above
17-Boiler 8 Status
30025
Boiler 8 Status
(PWM Boiler 8)
Input
0x0018 / 24
Same As Above
18-Net Blr 1 Status
30026
Net Boiler 1
Input
0x0019 / 25
Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
121 = On Line But Disabled
122 = On Line But Faulted
19-Net Blr 2 Status
30027
Net Boiler 2
Input
0x001A / 26
Same As Above
20-Net Blr 3 Status
30028
Net Boiler 3
Input
0x001B / 27
Same As Above
21-Net Blr 4 Status
30029
Net Boiler 4
Input
0x001C / 28
Same As Above
22-Net Blr 5 Status
30030
Net Boiler 5
Input
0x001D / 29
Same As Above
23-Net Blr 6 Status
30031
Net Boiler 6
Input
0x001E / 30
Same As Above
24-Net Blr 7 Status
30032
Net Boiler 7
Input
0x001F / 31
Same As Above