7.4.1 ProtoNode LER LED Locations and Functions
Figure 7-6: AERCO/ProtoNode Gateway LER ProtoCessor Board LED Locations
Table 7-3: ProtoNode LER LED Functions
LED
DESCRIPTION
Power
The power LED should show steady green at all times when the ProtoNode LER is powered.
System Error
The SYS ERR LED will flash once on power up and flash once 15 seconds after power up. A steady
red light will indicate there is a system error on the ProtoNode LER. If this occurs, immediately
report the related “system error” shown in the error screen of the RUI interface to AERCO
International for evaluation.
Comm. Error
The COMM ERR LED will flash once on power up and flash once 15 seconds after power up. A
steady red light will indicate a communication error has occurred. To establish the cause of the
error, go to the error screen of the RUI interface.
Config. Error
The Config ERR LED will flash once on power up and flash once 15 seconds after power up. A
steady amber light will indicate a configuration error exists in the active configuration. See the
Error Screen in the Remote User Interface for a description of the configuration error.
Node Offline
The Node Offline LED will flash once on power up and flash once 15 seconds after power up. If
the Node Offline LED stays lit, a Node Offline condition has occurred. Refer to Section 7.5.
RUN (PIO)
The RUN LED will start flashing 20 seconds after power indicating normal operation. The
ProtoNode LER will be able to access RUInet once this LED starts flashing.
PIC Run
The PIC RUN LED will flash indicating normal operation.
PIC Error
The PIC ERR LED will go on solid indicating there is a PIC error.
LON-TX
On normal operation of ProtoNode LER, the TX LED will flash when a message is sent on the Lon
port of the ProtoNode.
LON-RX
On normal operation of ProtoNode LER, the RX LED will flash when a message is received on the
Lon port of the ProtoNode.
LON-SRV
The LON-SRV LED will flash if the ProtoNode is configured for implicit addressing and not
commissioned. LED will be off if the ProtoNode is configured for implicit addressing and
commissioned or if it is configured for explicit addressing.
LON TX
LON RX
LON-SRV
Comm. Error
Run (PIO)
Config. Error
System Error
Node Offline
PIC Error
Unused
Unused
PIC Run
Power