Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
21
06-Over Temp
Alarm
unitstat_21
AV:216
data
float
216
nvoEcsStat21
inc count (9)
Output (non-polled)
30075/21
21
07-Flow Rate
flowrate_21
AV:217
data
float
217
nvoEcsFlow21
inc count (9)
Output (non-polled)
30291/21
E Valve Addr 22
22
01-Cntl Output
Signal
boilerstate_22
AV:221
data
float
221
nvoEcsState22
inc count (9)
Output (non-polled)
30004/22
22
02-Setpoint
effectsetpt_22
AV:222
data
float
222
nvoEcsSetpt22
inc count (9)
Output (non-polled)
30006/22
22
03-RmSetpt
rmsetpt_22
AV:223
data
float
223
nviEcsSetptRq22
inc count (9)
Input (non-polling)
40027/22
22
04-Outlet Temp
localsuptemp_2
2
AV:224
data
float
224
nvoEcsSupTmp22
inc count (9)
Output (non-polled)
30002/22
22
05-FBk Sensor
Temp
localrettemp_22
AV:225
data
float
225
nvoEcsRetTmp22
inc count (9)
Output (non-polled)
30290/22
22
06-Over Temp
Alarm
unitstat_22
AV:226
data
float
226
nvoEcsStat22
inc count (9)
Output (non-polled)
30075/22
22
07-Flow Rate
flowrate_22
AV:227
data
float
227
nvoEcsFlow22
inc count (9)
Output (non-polled)
30291/22
BMS Addr 128 – for C-More Controller Interface
128
01-Fire Rate Out
boilerstate_128
AV:260
data
float
228
nvoBlrState128
inc count (9)
Output (non-polled)
30005/128
128
02-Header Set
Temp
effectsetpt_128
AV:261
data
float
229
nvoEffSetpt128
inc count (9)
Output (non-polled)
30006/128
128
03-Net Header Set
Temp
setpt_128
AV:262
data
float
230
nviSetpt128
inc count (9)
Input (non-polling)
40005/128
128
04-Header Temp
localsuptemp_1
28
AV:263
data
float
231
nvoLocSupTmp128
inc count (9)
Output (non-polled)
30002/128
128
05-Outside Air
Temp
localoatemp_12
8
AV:264
data
float
232
nvoLocOATmp128
inc count (9)
Output (non-polled)
30003/128
128
06-Display Code
dispcode_128
AV:265
data
float
233
nvoDispCode128
inc count (9)
Output (non-polled)
30011/128