Appendix D: C-More Status and Fault Messages

Code

Message

Description

17

IGN SWTCH OPEN
DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel valve opened
during ignition.

18

AIRFLOW FAULT
DURING IGN

The Blower Proof Switch opened during ignition.

19

AIRFLOW FAULT
DURING RUN

The Blower Proof Switch opened during run.

20

SSOV FAULT
DURING IGN

The SSOV switch closed or failed to open during ignition.

21

SSOV FAULT
DURING RUN

The SSOV switch closed for more than 15 seconds during run.

22

FLAME LOSS
DURING IGN

The Flame signal was not seen during ignition or lost within 5
seconds after ignition.

23

FLAME LOSS
DURING RUN

The Flame signal was lost during run.

24

HIGH EXHAUST
TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

25

LOSS OF POWER

A power loss occurred. The time and date when power was
restored is displayed.

26

LOSS OF SENSOR

Not Currently Used

27

LOSS OF SIGNAL

Not Currently Used

28

HIGH O2 LEVEL

Not Currently Used

29

LOW O2 LEVEL

Not Currently Used

30

HIGH CO LEVEL

Not Currently Used

31

SSOV RELAY FAILURE

A failure has been detected in one of the

relays that control the SSOV.

32

RESIDUAL
FLAME

The Flame signal was seen for more than 60 seconds during
standby.

33

HEAT DEMAND
FAILURE

The Heat Demand Relays on the Ignition board failed to activate
when commanded.

34

IGN SWTCH CLOSED
DURING PURGE

The Ignition Position Limit switch on the Air/Fuel valve closed
during purge.

35

PRG SWTCH CLOSED
DURING IGNITION

The Purge Position Limit switch on the Air/Fuel valve closed
during ignition.

36

SSOV SWITCH OPEN

The SSOV switch opened during standby.

37

IGNITION BOARD COMM
FAULT

Communication fault between the Ignition board and the CPU
board.

38

WAIT

Prompts the operator to wait.