AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 93 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon

Direction

ModBus/

Unit

Address

4

02-Target Setpoint

effectsetpt_16

AV:152

data
float

152

nvoMlxSetpt16

inc count (9)

Output (non-polled)

41019/16

4

03-Req Outlet
Temp

setpt_16

AV:153

data
float

153

nviMlxSetptRq16

inc count (9)

Input (non-polling)

41005/16

4

04-Net Direct Drive

boilercmd_4

AV:154

data
float

154

nviMlxCmd4

inc count (9)

Input (non-polling)

40002/4

C-More Addr 5

5

01-Fire Rate Out

boilerstate_5

AV:41

data
float

41

nvoBlrState5

inc count (9)

Output (non-polled)

30009/5

5

02-Active Setpoint

effectsetpt_5

AV:42

data
float

42

nvoEffSetpt5

inc count (9)

Output (non-polled)

30017/5

5

03-Net Remote
Setpt

setpt_5


AV:43

data
float

43

nviSetpt5

inc count (9)

Input (non-polling)

40001/5

5

05-Fire Rate In

boilerload_5

AV:45

data
float

45

nvoBlrLoad5

inc count (9)

Output (non-polled)

30018/5

5

06-Outlet Temp

localsuptemp_5

AV:46

data
float

46

nvoLocSupTmp5

inc count (9)

Output (non-polled)

30003/5

5

07-Display Code

dispcode_5

AV:47

data
float

47

nvoDispCode5

inc count (9)

Output (non-polled)

30001/5

5

08-Unit Status

unitstat_5

AV:48

data
float

48

nvoUnitStat5

inc count (9)

Output (non-polled)

30002/5

5

09-Run Cycles

runcycles_5

AV:49

data
float

49

nvoRunCycles5

51

Output (non-polled)

30012-
30013/5

5

10-Run Hours

runhours_5

AV:50

data
float

50

nvoRunHours5

51

Output (non-polled)

30014-
30015/5

C-More Addr 6

6

01-Fire Rate Out

boilerstate_6

AV:51

data
float

51

nvoBlrState6

inc count (9)

Output (non-polled)

30009/6

6

02-Active Setpoint

effectsetpt_6

AV:52

data
float

52

nvoEffSetpt6

inc count (9)

Output (non-polled)

30017/6

6

03-Net Remote
Setpt

setpt_6

AV:53

data
float

53

nviSetpt6

inc count (9)

Input (non-polling)

40001/6

6

05-Fire Rate In

boilerload_6

AV:55

data
float

55

nvoBlrLoad6

inc count (9)

Output (non-polled)

30018/6