Appendix F:
BCM AND BMM FAULT CODES FOR MODULEX E8
CONTROLLER
Appendix F.1: BCM and BMM Fault Code Conversion Table
Table F-1, below, shows how to interpret the displayed fault code in the E8 Controller display,
while Table F-2, on the next page, shows a description of the fault and troubleshooting tips
associated with the BMMs. Table F-3, following, is for BCM faults.
In order to derive the correct error code from what is shown in the E8 Controller display, use
Table F-1, below, to determine the working error code. To use the table, identify the displayed
number from the first column, identify the affected module from the second column, apply the
formula from the third column, and identify the Error Table to reference from the fourth column.
Table F-1: BCM and BMM Fault Code Conversion Table
Observed Code
Observed
Code
Code to Look Up in
Table
Code = 0
N/A
No Fault
-
Code between 1 and 255
BMM #0 Fault
Look up code
F-2
Code between 256 and 511
BMM #1 Fault
Subtract 256 from reading
F-2
Code between 512 and 767
BMM #2 Fault
Subtract 512 from reading
F-2
Code between 768 and 1023
BMM #3 Fault
Subtract 768 from reading
F-2
Code between 1024 and 1279
BMM #4 Fault
Subtract 1024 from reading
F-2
Code between 1280 and 1535
BMM #5 Fault
Subtract 1280 from reading
F-2
Code between 1536 and 1791
BMM #6 Fault
Subtract 1536 from reading
F-2
Code between 1792 and 2047
BMM #7 Fault
Subtract 1792 from reading
F-2
Code between 2048 and 65279
N/A
Invalid Codes
-
Code above 65280
BCM Fault
Subtract 65280 from reading
F-2
Example:
Based on the above, a code reading of “261” means the fault occurred on BMM #1.
The fault code is (261 – 256 = ) 5. An Error Code of 5 from the BMM Fault Codes
table means “Flame Loss During Run”.