Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 68

background image

AERCO ProtoNode Gateway

User Manual

Page 68 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

Table C-2: Eight C-Mores and One ACS/BMS II/BMS

Equip

Point Name

Name

Read

Only

BACnet

Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon Direction

ModBus/

Unit Address

3

10-Run Hours

runhours_3

AV:59

data

float

30 nvoRunHours3

51

Output (non-polled)

30014-

30015/3

3

11-Oxygen

o2level_3

AV:163

data

float

163 nvoO2Lev3

inc count (9)

Output (non-polled)

30010/3

3

12-Exhaust Temp

exhtemp_3

AV:183

data

float

183 nvoExhTmp3

inc count (9)

Output (non-polled)

30007/3

Blr Addr 4

4

01-Fire Rate Out

boilerstate_4

AV:70

data

float

31 nvoBlrState4

inc count (9)

Output (non-polled)

30009/4

4

02-Active Setpoint

effectsetpt_4

AV:71

data

float

32 nvoEffSetpt4

inc count (9)

Output (non-polled)

30017/4

4

03-Net Remote Setpt setpt_4

AV:72

data

float

33 nviSetpt4

inc count (9)

Input (non-polling)

40001/4

4

05-Fire Rate In

boilerload_4

AV:73

data

float

35 nvoBlrLoad4

inc count (9)

Output (non-polled)

30018/4

4

06-Outlet Temp

localsuptemp_

4

AV:65

data

float

36 nvoLocSupTmp4 inc count (9)

Output (non-polled)

30003/4

4

07-Display Code

dispcode_4

AV:66

data

float

37 nvoDispCode4

inc count (9)

Output (non-polled)

30001/4

4

08-Unit Status

unitstat_4

AV:67

data

float

38 nvoUnitStat4

inc count (9)

Output (non-polled)

30002/4

4

09-Run Cycles

runcycles_4

AV:68

data

float

39 nvoRunCycles4

51

Output (non-polled)

30012-

30013/4

4

10-Run Hours

runhours_4

AV:69

data

float

40 nvoRunHours4

51

Output (non-polled)

30014-

30015/4

4

11-Oxygen

o2level_4

AV:164

data

float

164 nvoO2Lev4

inc count (9)

Output (non-polled)

30010/4

4

12-Exhaust Temp

exhtemp_4

AV:184

data

float

184 nvoExhTmp4

inc count (9)

Output (non-polled)

30007/4

Blr Addr 5

5

01-Fire Rate Out

boilerstate_5

AV:80

data

float

41 nvoBlrState5

inc count (9)

Output (non-polled)

30009/5

5

02-Active Setpoint

effectsetpt_5

AV:81

data

float

42 nvoEffSetpt5

inc count (9)

Output (non-polled)

30017/5