Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 78

AERCO ProtoNode Gateway
User Manual
Page 78 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/U
nit Address
6
06-Outlet Temp
localsuptemp_6
AV:85
data
float
56
nvoLocSupTmp6
inc count (9)
Output (non-polled)
30003/6
6
07-Display Code
dispcode_6
AV:86
data
float
57
nvoDispCode6
inc count (9)
Output (non-polled)
30001/6
6
08-Unit Status
unitstat_6
AV:87
data
float
58
nvoUnitStat6
inc count (9)
Output (non-polled)
30002/6
6
09-Run Cycles
runcycles_6
AV:88
data
float
59
nvoRunCycles6
51
Output (non-polled)
30012-
30013/6
6
10-Run Hours
runhours_6
AV:89
data
float
60
nvoRunHours6
51
Output (non-polled)
30014-
30015/6
6
11-Oxygen
o2level_6
AV:166
data
float
166 nvoO2Lev6
inc count (9)
Output (non-polled)
30010/6
6
12-Exhaust Temp exhtemp_6
AV:186
data
float
186 nvoExhTmp6
inc count (9)
Output (non-polled)
30007/6
Blr Addr 7
7
01-Fire Rate Out boilerstate_7
AV:100
data
float
61
nvoBlrState7
inc count (9)
Output (non-polled)
30009/7
7
02-Active
Setpoint
effectsetpt_7
AV:101
data
float
62
nvoEffSetpt7
inc count (9)
Output (non-polled)
30017/7
7
03-Net Remote
Setpt
setpt_7
AV:102
data
float
63
nviSetpt7
inc count (9)
Input (non-polling)
40001/7
7
05-Fire Rate In
boilerload_7
AV:94
data
float
65
nvoBlrLoad7
inc count (9)
Output (non-polled)
30018/7
7
06-Outlet Temp
localsuptemp_7
AV:95
data
float
66
nvoLocSupTmp7
inc count (9)
Output (non-polled)
30003/7
7
07-Display Code
dispcode_7
AV:96
data
float
67
nvoDispCode7
inc count (9)
Output (non-polled)
30001/7
7
08-Unit Status
unitstat_7
AV:97
data
float
68
nvoUnitStat7
inc count (9)
Output (non-polled)
30002/7
7
09-Run Cycles
runcycles_7
AV:98
data
float
69
nvoRunCycles7
51
Output (non-polled)
30012-
30013/7