beautypg.com

1 baud rate dip switch selection, Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 11

background image

AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 11 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

2.4.3 ProtoNode RER: Setting the Node-ID for Metasys N2 and Modbus/TCP

• Set DIP switches A0 – A7 to assign Node-ID for Metasys N2 and Modbus TCP for

the ProtoNode RER.

• Metasys N2 and Modbus/TCP Node-ID Addressing: Metasys N2 and Modbus/TCP

Node-ID’s range from 1-255

Please refer to Appendix A.3 for the full range of addresses to set Node-ID/Device Instance.

2.4.4 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP

• DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate

provided by the Building Automation System for BACnet MS/TP.

• DIP Switches B0 – B3 are disabled on ProtoNode LER (FPC-N35 LonWorks).
• The baud rate on the ProtoNode for Metasys N2 is set for 9600. DIP Switches B0 –

B3 are disabled for Metasys N2 on ProtoNode RER (FPC-N34).

B0 B1 B2 B3

FIGURE 2-3: MAC Address DIP Switches

NOTE

When setting DIP Switches, please ensure that power to the
board is OFF.

2.4.4.1 Baud Rate DIP Switch Selection

TABLE 2-3: Baud Rate DIP Switch Settings

Baud

B0

B1

B2

B3

9600

ON

ON

ON

Off

19200

Off

Off

Off

ON

38400

ON

ON

Off

ON

57600

Off

Off

ON

ON

76800

ON

Off

ON

ON