Aerco protonode gateway, User manual, Table c-4: four modulex and one acs/bms ii – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 87
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 87 of 126
GF-129
Ph.: 800-526-0288
11/06/2014
Table C-4: Four Modulex and One ACS/BMS II
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
2
08-Unit Status
unitstat_2
AV:151
data
float
161
nvoMlxStat2
inc count (9)
Output (non-polled)
30002/2
2
09-Ret Flow Temp
returntemp_2
AV:5
data
float
162
nvoMlxRetTmp2
inc count (9)
Output (non-polled)
41004/2
Mlx Addr 3
3
01-Act Mod Lev
boilerstate_3
AV:18
data
float
164
nvoMlxState3
inc count (9)
Output (non-polled)
41009/3
3
02-Target Setpoint
effectsetpt_3
AV:19
data
float
165
nvoMlxSetpt3
inc count (9)
Output (non-polled)
41019/3
3
03-Req Outlet
Temp
setpt_3
AV:20
data
float
166
nviMlxSetptRq3
inc count (9)
Input (non-polling)
41005/3
3
04-Net Direct Drive
boilercmd_3
AV:21
data
float
167
nviMlxCmd3
inc count (9)
Input (non-polling)
40002/3
3
05-Mod Lev In
boilerload_3
AV:22
data
float
168
nvoMlxLoad3
inc count (9)
Output (non-polled)
41201/3
3
06-Flow Sens
Temp
localsuptemp_3
AV:23
data
float
169
nvoMlxSupTmp3
inc count (9)
Output (non-polled)
41003/3
3
07-Display Code
dispcode_3
AV:24
data
float
170
nvoMlxDispCode3
inc count (9)
Output (non-polled)
30001/3
3
11-Error Code
errcode_3
AV:7
data
float
171
nvoMlxErrCode3
51
Output (non-polled)
40001/3
3
08-Unit Status
unitstat_3
AV:25
data
float
172
nvoMlxStat3
inc count (9)
Output (non-polled)
30002/3
3
09-Ret Flow Temp
returntemp_3
AV:8
data
float
173
nvoMlxRetTmp3
inc count (9)
Output (non-polled)
41004/3
Mlx Addr 4
4
01-Act Mod Lev
boilerstate_4
AV:28
data
float
175
nvoMlxState4
inc count (9)
Output (non-polled)
41009/4
4
02-Target Setpoint
effectsetpt_4
AV:29
data
float
176
nvoMlxSetpt4
inc count (9)
Output (non-polled)
41019/4
4
03-Req Outlet
Temp
setpt_4
AV:30
data
float
177
nviMlxSetptRq4
inc count (9)
Input (non-polling)
41005/4
4
04-Net Direct Drive
boilercmd_4
AV:42
data
float
178
nviMlxCmd4
inc count (9)
Input (non-polling)
40002/4