Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 77
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 77 of 126
GF-129
Ph.: 800-526-0288
11/06/2014
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/U
nit Address
5
01-Fire Rate Out
boilerstate_5
AV:80
data
float
41
nvoBlrState5
inc count (9)
Output (non-polled)
30009/5
5
02-Active
Setpoint
effectsetpt_5
AV:81
data
float
42
nvoEffSetpt5
inc count (9)
Output (non-polled)
30017/5
5
03-Net Remote
Setpt
setpt_5
AV:82
data
float
43
nviSetpt5
inc count (9)
Input (non-polling)
40001/5
5
05-Fire Rate In
boilerload_5
AV:74
data
float
45
nvoBlrLoad5
inc count (9)
Output (non-polled)
30018/5
5
06-Outlet Temp
localsuptemp_5
AV:75
data
float
46
nvoLocSupTmp5
inc count (9)
Output (non-polled)
30003/5
5
07-Display Code
dispcode_5
AV:76
data
float
47
nvoDispCode5
inc count (9)
Output (non-polled)
30001/5
5
08-Unit Status
unitstat_5
AV:77
data
float
48
nvoUnitStat5
inc count (9)
Output (non-polled)
30002/5
5
09-Run Cycles
runcycles_5
AV:78
data
float
49
nvoRunCycles5
51
Output (non-polled)
30012-
30013/5
5
10-Run Hours
runhours_5
AV:79
data
float
50
nvoRunHours5
51
Output (non-polled)
30014-
30015/5
5
11-Oxygen
o2level_5
AV:165
data
float
165 nvoO2Lev5
inc count (9)
Output (non-polled)
30010/5
5
12-Exhaust Temp exhtemp_5
AV:185
data
float
185 nvoExhTmp5
inc count (9)
Output (non-polled)
30007/5
Blr Addr 6
6
01-Fire Rate Out
boilerstate_6
AV:90
data
float
51
nvoBlrState6
inc count (9)
Output (non-polled)
30009/6
6
02-Active
Setpoint
effectsetpt_6
AV:91
data
float
52
nvoEffSetpt6
inc count (9)
Output (non-polled)
30017/6
6
03-Net Remote
Setpt
setpt_6
AV:92
data
float
53
nviSetpt6
inc count (9)
Input (non-polling)
40001/6
6
05-Fire Rate In
boilerload_6
AV:84
data
float
55
nvoBlrLoad6
inc count (9)
Output (non-polled)
30018/6