Aerco protonode gateway, User manual, Table c-4: four modulex and one acs/bms ii – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 88
AERCO ProtoNode Gateway
User Manual
Page 88 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
Table C-4: Four Modulex and One ACS/BMS II
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
4
05-Mod Lev In
boilerload_4
AV:43
data
float
179
nvoMlxLoad4
inc count (9)
Output (non-polled)
41201/4
4
06-Flow Sens
Temp
localsuptemp_4
AV:44
data
float
180
nvoMlxSupTmp4
inc count (9)
Output (non-polled)
41003/4
4
07-Display Code
dispcode_4
AV:45
data
float
181
nvoMlxDispCode4
inc count (9)
Output (non-polled)
30001/4
4
11-Error Code
errcode_4
AV:10
data
float
182
nvoMlxErrCode4
51
Output (non-polled)
40001/4
4
08-Unit Status
unitstat_4
AV:46
data
float
183
nvoMlxStat4
inc count (9)
Output (non-polled)
30002/4
4
09-Ret Flow Temp
returntemp_4
AV:11
data
float
184
nvoMlxRetTmp4
inc count (9)
Output (non-polled)
41004/4