beautypg.com

Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 114

background image

AERCO ProtoNode Gateway

User Manual

Page 114 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2 Type

N2

ID

Lon SNVT

NAME

Lon

SNVT

Lon Direction

ModBus
Address

247

Next Turn-On

Percent

SMD_BAS_IP_OpVal_[15]

AV:115

Data Float

21

nvoOpVal_16

inc count (9)

Output (non-polled)

30115

247

Header High Limit

SMD_BAS_IP_OpVal_[16]

AV:116

Data Float

22

nvoOpVal_17

inc count (9)

Output (non-polled)

30116

247

Header Low Limit

SMD_BAS_IP_OpVal_[17]

AV:117

Data Float

23

nvoOpVal_18

inc count (9)

Output (non-polled)

30117

247

Header Temp High

Limit

SMD_BAS_IP_OpVal_[18]

AV:118

Data Float

24

nvoOpVal_19

inc count (9)

Output (non-polled)

30118

247

Header Setpoint

Mode

SMD_BAS_IP_OpVal_[19]

AV:119

Data Float

25

nvoOpVal_20

inc count (9)

Output (non-polled)

30119

Write Master Operating Values

247

Setpt

SMD_BAS_IP_CtrlVal_[0]

AV:200

Data Float

26

nvoCtrlVal_1 inc count (9)

Input (non-polling)

40200

247

Setback Setpt

SMD_BAS_IP_CtrlVal_[1]

AV:201

Data Float

27

nvoCtrlVal_2 inc count (9)

Input (non-polling)

40201

247

Setback Start

SMD_BAS_IP_CtrlVal_[2]

AV:202

Data Float

28

nvoCtrlVal_3 inc count (9)

Input (non-polling)

40202

247

Setback End

SMD_BAS_IP_CtrlVal_[3]

AV:203

Data Float

29

nvoCtrlVal_4 inc count (9)

Input (non-polling)

40203