Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 114
AERCO ProtoNode Gateway
User Manual
Page 114 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon SNVT
NAME
Lon
SNVT
Lon Direction
ModBus
Address
247
Next Turn-On
Percent
SMD_BAS_IP_OpVal_[15]
AV:115
Data Float
21
nvoOpVal_16
inc count (9)
Output (non-polled)
30115
247
Header High Limit
SMD_BAS_IP_OpVal_[16]
AV:116
Data Float
22
nvoOpVal_17
inc count (9)
Output (non-polled)
30116
247
Header Low Limit
SMD_BAS_IP_OpVal_[17]
AV:117
Data Float
23
nvoOpVal_18
inc count (9)
Output (non-polled)
30117
247
Header Temp High
Limit
SMD_BAS_IP_OpVal_[18]
AV:118
Data Float
24
nvoOpVal_19
inc count (9)
Output (non-polled)
30118
247
Header Setpoint
Mode
SMD_BAS_IP_OpVal_[19]
AV:119
Data Float
25
nvoOpVal_20
inc count (9)
Output (non-polled)
30119
Write Master Operating Values
247
Setpt
SMD_BAS_IP_CtrlVal_[0]
AV:200
Data Float
26
nvoCtrlVal_1 inc count (9)
Input (non-polling)
40200
247
Setback Setpt
SMD_BAS_IP_CtrlVal_[1]
AV:201
Data Float
27
nvoCtrlVal_2 inc count (9)
Input (non-polling)
40201
247
Setback Start
SMD_BAS_IP_CtrlVal_[2]
AV:202
Data Float
28
nvoCtrlVal_3 inc count (9)
Input (non-polling)
40202
247
Setback End
SMD_BAS_IP_CtrlVal_[3]
AV:203
Data Float
29
nvoCtrlVal_4 inc count (9)
Input (non-polling)
40203