4.6 Commissioning ProtoNode FPC-N35 on a LonWorks Network
Commissioning may only be performed by the LonWorks administrator. The User
will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoNode
FPC-N35 at the correct step of the Commissioning process which is different for each
LonWorks Network Management Tool.
If an XIF file is required, see steps in Section 4.7 to generate XIF
Figure 4-6: LonWorks Service Pin Location
4.7 Instructions to Upload XIF File from ProtoNode FPC-N35 Using
FieldServer GUI Web Server
Connect a standard cat5 Ethernet cable between the PC and ProtoNode.
The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If
the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC
on the 192.168.1.xxx network.
• For Windows XP:
Go to
>
>
Right-click on Local Area Connection > Properties
Highlight
>
• For Windows 7:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>