Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon

Direction

ModBus/

Unit

Address

11

09-Run Cycles

runcycles_11

AV:109

data
float

109

nvoRunCycles11

51

Output (non-polled)

30012-
30013/11

11

10-Run Hours

runhours_11

AV:110

data
float

110

nvoRunHours11

51

Output (non-polled)

30014-
30015/11

C-More Addr 12

12

01-Fire Rate Out

boilerstate_12

AV:111

data
float

111

nvoBlrState12

inc count (9)

Output (non-polled)

30009/12

12

02-Active Setpoint

effectsetpt_12

AV:112

data
float

112

nvoEffSetpt12

inc count (9)

Output (non-polled)

30017/12

12

03-Net Remote
Setpt

setpt_12

AV:113

data
float

113

nviSetpt12

inc count (9)

Input (non-polling)

40001/12

12

05-Fire Rate In

boilerload_12

AV:115

data
float

115

nvoBlrLoad12

inc count (9)

Output (non-polled)

30018/12

12

06-Outlet Temp

localsuptemp_1
2

AV:116

data
float

116

nvoLocSupTmp12

inc count (9)

Output (non-polled)

30003/12

12

07-Display Code

dispcode_12

AV:117

data
float

117

nvoDispCode12

inc count (9)

Output (non-polled)

30001/12

12

08-Unit Status

unitstat_12

AV:118

data
float

118

nvoUnitStat12

inc count (9)

Output (non-polled)

30002/12

12

09-Run Cycles

runcycles_12

AV:119

data
float

119

nvoRunCycles12

51

Output (non-polled)

30012-
30013/12

12

10-Run Hours

runhours_12

AV:120

data
float

120

nvoRunHours12

51

Output (non-polled)

30014-
30015/12

C-More Addr 13

13

01-Fire Rate Out

boilerstate_13

AV:1

data
float

1

nvoBlrState13

inc count (9)

Output (non-
polled)

30009/13

13

02-Active Setpoint

effectsetpt_13

AV:2

data
float

2

nvoEffSetpt13

inc count (9)

Output (non-
polled)

30017/13

13

03-Net Remote
Setpt

setpt_13

AV:3

data
float

3

nviSetpt13

inc count (9)

Input (non-polling)

40001/13

13

05-Fire Rate In

boilerload_13

AV:5

data
float

5

nvoBlrLoad13

inc count (9)

Output (non-
polled)

30018/13

13

06-Outlet Temp

localsuptemp_1
3

AV:6

data
float

6

nvoLocSupTmp13

inc count (9)

Output (non-
polled)

30003/13