beautypg.com

Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 22

background image

AERCO ProtoNode Gateway

User Manual

Page 22 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

3.8.1.2 Setting the PMC Board RS-485 DIP Switches Instructions

The 4-position RS485 DIP Switch (S2) on the PMC PCB of the C-More Controller must be
set as follows for use with the ProtoNode:

• The termination (TERM) and bias (BIAS1 & BIAS2) DIP Switches of S2 must be set

to DISABLE.

• If an Oxygen Sensor is connected to the C-More Controller, switch R1 (see below)

should be set to DISABLED (down). If an Oxygen Sensor is NOT connected to the
C-More Controller, it should be set to ENABLED (up). Improper setting of R1 may
result in error messages.

















Figure 3-12: C-More Controller PCB DIP Switch Settings

NOTE

If bias is needed, activate the ProtoNode bias jumpers. If
termination is needed, .activate the ProtoNode termination
jumpers as well as the termination dip switch in the last
boiler/heater’s I/O box at the end of the RS485 daisy chain.

If an Oxygen Sensor is attached to the C-
More Controller, set R1 to DISABLED
(down). If an Oxygen Sensor is NOT used,
set R1 to ENABLED (up). Factory default
setting is ENABLED.

ENABLE

DISABLE

BI

A

S

2

T

ER

M

BI

A

S1

R1

S2

RS485

R1