Appendix D: C-More Status and Fault Messages

Code

Message

Description

58

WARNING IN WTR TEMP
HIGH

Inlet water temperature is getting too high.

59

WARNING IN WTR TEMP
HIGH

Inlet water temperature is getting too low.

60

INLET GAS PRESS
SENSOR OPEN

Inlet gas pressure switch is open.

61

GAS PLATE DP SENSOR
OPEN

Gas plate differential pressure switch is open.

62

O2 PERCENTAGE LOW

Oxygen level is too low.

63

O2 SENSOR
MALFUNCTION

Oxygen sensor reading is out of range.

64

WARNING O2 LEVEL HIGH Oxygen level is too high.

65

RECIRC PUMP FAILURE

Heater recirculation pump has malfunctioned.

66

IGNITION MONITOR X SEC Waiting for proof of ignition.

67

NO FLOW SAFETY
LOCKOUT

Flow input not registering when boiler is starting up.

68

IGNITION SPARK FAULT

No ignition current measured when igniter is energized.

69

PRE IGNITION X SEC

Waiting for SSOV to prove open.

70

CLEANING IGNITER X SEC Ignition transformer is energized with SSOV closed.

71

TOO MANY CYCLES IN 24
HOURS

The number of cycles in 24 hour period has been exceeded.

72

TOO MANY OVRTMPS IN
24 HOURS

The number of over temperature events in 24 hour period has
been exceeded.

73

AIR SENSOR FAULT

The inlet air sensor is out of range.

74

Auto Diagnostic Mode
ACTIVE

Informational message.

75

Auto Diagnostic Mode
COMPLETED

Informational message.

76

Auto Diagnostic Mode
ABORTED

Informational message.

77

DHW HEATING ACTIVE Domestic Hot Water is enabled. Message shows when in

combo mode with a fault in the drive signal.

78

Cooling Heat Exchanger

Informational message during slow shutdown mode.

79

BST NETWORK TEMP
SENSOR FAULT

The BST Modbus header temperature sensor is out of range.

80

BST NETWORK TEMP
COM FAULT

The BST Modbus failed to read the header temperature
sensor.

81

BST LOCAL HEADER
SENSOR FAULT

The BST direct connected header temperature sensor is out of
range.