Appendix B.3: AERCO ACS/BMS II & BCM Point Definitions

Table B-3: AERCO ACS/BMS II & BCM Point Definitions (Cont.)

Point Name

BAS Modbus

Data Address

GF-108, GF-
124, GF-114

Point Name

Reg.

Type

Modbus Data

Address (Hex/Dec.)

Units (Range)

Boiler Management System (BMS II) or AERCO Control System (ACS)

01-Fire Rate Out

30005

Fire Rate Out

Input

0x0004 / 4

% (0 to 100)

02-Header Set Temp

30006

Header Set
Temperature

Input

0x0005 / 5

°F (40 to 220)

03-Net Header Set
Temp

40005

Net Header Set
Temp

Holding

0x0004 / 4

°F (40 to 220)

04-Header Temp

30002

Header
Temperature

Input

0x0001 / 1

°F (40 to 220)

05-Outside Air Temp

30003

Outside Air
Temperature

Input

0x0002 / 2

°F (-60 to 120)

06-Display Code

30011

Fault/Message
Code

Input

0x000A / 10

Bit (0 to 65535)
Bit 0 = Outside Air Sensor
Error
Bit 1 = Header Sensor
Error
Bit 2 = Interlock 1 Error
Bit 3 = Interlock 2 Error
Bit 4 = Indoor Air/Return
Sens Error
Bit 5 = 4-20 mA Input Error

07-Num Boilers
Fired

30008

Total Boilers Fired

Input

0x0007 / 7

(0 to 32)

08-Num Boilers
Online

30009

Total Boilers On
Line

Input

0x0008 / 8

(0 to 32)

09-Last Blr Fired

30017

Last Boiler Fired
(corr. for Lead
Boiler Number)

Input

0x0010 / 16

(1 to 32)

18-Net Blr 1 Status

30026

Net Boiler 1

Input

0x0019 / 25

Enum (1 to 40, 119, 120)
1 to 40 = Fired and
Sequence
119 = Not On Line
120 = On Line But Not
Fired
121 = On Line But
Disabled
122 = On Line But Faulted

19-Net Blr 2 Status

30027

Net Boiler 2

Input

0x001A / 26

Same As Above

20-Net Blr 3 Status

30028

Net Boiler 3

Input

0x001B / 27

Same As Above

21-Net Blr 4 Status

30029

Net Boiler 4

Input

0x001C / 28

Same As Above

Modulex Boiler with BCM

01-Act Mod Lev
(Actual Modulation
Level)

41009

Global Actual
Modulation Level

Holding

0x03F0 / 1008

% (0 to 100)

02-Target Setpoint

41019

Target Setpoint

Holding

0x03F8 / 1016

°F (32 to 185) (Value x 10)

03-Req Outlet Temp
(Requested Outlet
Temp)

41005

Requested
Setpoint

Holding

0x03EC / 1004

°F (32 to 185) (Value x 10)

04-Net Direct Drive

40002

Direct Drive
Requested
Modulation Level

Holding

0x0001 / 1

% (0 to 100)

05-Mod Lev In
(Modulation Level In)

41201

Monitor Only
Global Modulation
Level
from Cascade
Manager

Holding

0x04B0 / 1200

% (0 to 100)