Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 74
AERCO ProtoNode Gateway
User Manual
Page 74 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
Appendix C.3: Twelve C-Mores and One ACS/BMS II/BMS
TABLE C-3: Twelve C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/U
nit Address
Blr Addr 1
1
01-Fire Rate Out
boilerstate_1
AV:26
data
float
1
nvoBlrState1
inc count (9)
Output (non-polled)
30009/1
1
02-Active
Setpoint
effectsetpt_1
AV:27
data
float
2
nvoEffSetpt1
inc count (9)
Output (non-polled)
30017/1
1
03-Net Remote
Setpt
setpt_1
AV:24
data
float
3
nviSetpt1
inc count (9)
Input (non-polling)
40001/1
1
05-Fire Rate In
boilerload_1
AV:28
data
float
5
nvoBlrLoad1
inc count (9)
Output (non-polled)
30018/1
1
06-Outlet Temp
localsuptemp_1
AV:29
data
float
6
nvoLocSupTmp1
inc count (9)
Output (non-polled)
30003/1
1
07-Display Code
dispcode_1
AV:22
data
float
7
nvoDispCode1
inc count (9)
Output (non-polled)
30001/1
1
08-Unit Status
unitstat_1
AV:23
data
float
8
nvoUnitStat1
inc count (9)
Output (non-polled)
30002/1
1
09-Run Cycles
runcycles_1
AV:42
data
float
9
nvoRunCycles1
51
Output (non-polled)
30012-
30013/1
1
10-Run Hours
runhours_1
AV:43
data
float
10
nvoRunHours1
51
Output (non-polled)
30014-
30015/1
1
11-Oxygen
o2level_1
AV:161
data
float
161 nvoO2Lev1
inc count (9)
Output (non-polled)
30010/1
1
12-Exhaust Temp exhtemp_1
AV:181
data
float
181 nvoExhTmp1
inc count (9)
Output (non-polled)
30007/1
Blr Addr 2
2
01-Fire Rate Out
boilerstate_2
AV:30
data
float
11
nvoBlrState2
inc count (9)
Output (non-polled)
30009/2
2
02-Active
Setpoint
effectsetpt_2
AV:46
data
float
12
nvoEffSetpt2
inc count (9)
Output (non-polled)
30017/2
2
03-Net Remote
Setpt
setpt_2
AV:47
data
float
13
nviSetpt2
inc count (9)
Input (non-polling)
40001/2