Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 106
AERCO ProtoNode Gateway
User Manual
Page 106 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
Appendix C.7: Eight C-More Boilers/Heaters and BST/WHM Master
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon SNVT
NAME
Lon
SNVT
Lon Direction
ModBus
Address
Blr Addr 1
1
Comm Address
SMD_BAS_IP_HTR_01_[0]
AV:300
Data Float
46
nvoHTR_01_1 inc count (9)
Output (non-polled) 30300
1
Unit Status
SMD_BAS_IP_HTR_01_[1]
AV:301
Data Float
47
nvoHTR_01_2 inc count (9)
Output (non-polled) 30301
1
Fault Code
SMD_BAS_IP_HTR_01_[2]
AV:302
Data Float
48
nvoHTR_01_3 inc count (9)
Output (non-polled) 30302
1
Outlet Temp
SMD_BAS_IP_HTR_01_[3]
AV:303
Data Float
49
nvoHTR_01_4 inc count (9)
Output (non-polled) 30303
1
FFWD Temp
SMD_BAS_IP_HTR_01_[4]
AV:304
Data Float
50
nvoHTR_01_5 inc count (9)
Output (non-polled) 30304
1
Inlet Temp
SMD_BAS_IP_HTR_01_[5]
AV:305
Data Float
51
nvoHTR_01_6 inc count (9)
Output (non-polled) 30305
1
Exhaust Temp
SMD_BAS_IP_HTR_01_[6]
AV:306
Data Float
52
nvoHTR_01_7 inc count (9)
Output (non-polled) 30306
1
Air Temp
SMD_BAS_IP_HTR_01_[7]
AV:307
Data Float
53
nvoHTR_01_8 inc count (9)
Output (non-polled) 30307
1
Flame Strength
SMD_BAS_IP_HTR_01_[8]
AV:308
Data Float
54
nvoHTR_01_9 inc count (9)
Output (non-polled) 30308
1
Fire Rate In
SMD_BAS_IP_HTR_01_[9]
AV:309
Data Float
55
nvoHTR_01_10 inc count (9)
Output (non-polled) 30309
1
Fire Rate Out
SMD_BAS_IP_HTR_01_[10]
AV:310
Data Float
56
nvoHTR_01_11 inc count (9)
Output (non-polled) 30310
1
Unit Type
SMD_BAS_IP_HTR_01_[11]
AV:311
Data Float
57
nvoHTR_01_12 inc count (9)
Output (non-polled) 30311
1
Unit Size
SMD_BAS_IP_HTR_01_[12]
AV:312
Data Float
58
nvoHTR_01_13 inc count (9)
Output (non-polled) 30312
1
Value State
SMD_BAS_IP_HTR_01_[13]
AV:313
Data Float
59
nvoHTR_01_14 inc count (9)
Output (non-polled) 30313
1
Net Remote Setpt
SMD_BAS_IP_HTR_01_[14]
AV:314
Data Float
60
nvoHTR_01_15 inc count (9)
Output (non-polled) 30314
1
Run Cycles Upper
SMD_BAS_IP_HTR_01_[15]
AV:315
Data Float
61
nvoHTR_01_16 inc count (9)
Output (non-polled) 30315
1
Run Cycles Lower
SMD_BAS_IP_HTR_01_[16]
AV:316
Data Float
62
nvoHTR_01_17 inc count (9)
Output (non-polled) 30316
1
Run Hours Upper
SMD_BAS_IP_HTR_01_[17]
AV:317
Data Float
63
nvoHTR_01_18 inc count (9)
Output (non-polled) 30317
1
Run Hours Lower
SMD_BAS_IP_HTR_01_[18]
AV:318
Data Float
64
nvoHTR_01_19 inc count (9)
Output (non-polled) 30318
1
Oxygen Level
SMD_BAS_IP_HTR_01_[19]
AV:319
Data Float
65
nvoHTR_01_20 inc count (9)
Output (non-polled) 30319