beautypg.com

3 writing setpoint to aerco devices, Writing setpoint to aerco devices, Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 38: Step 3: send log, Step 4: close the program

background image

AERCO ProtoNode Gateway

User Manual

Page 38 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

Step 3: Send Log

Click the “Send Log” button located near the bottom of the dialog. The following dialog
should appear.

Figure 7-4: Send Log Dialog Box

Push the ‘Locate Folder’ button to launch explorer and have it point directly at the correct
folder. The file upload.zip must be sent to

[email protected]

.

Step 4: Close the Program

Press the exit button when the log is completed

7.3 Writing Setpoint to AERCO Devices

The administrator must setup their Building Automation System to write the Setpoint through the
gateway to the C-More, ACS or BMS II at least three times within the Network timeout. The
setpoint value to write is called “Net Remote Setpoint” in the C-More and “Net Header Set Point”
in the ACS and BMS II. See Point tables in Appendix B and C. See also Section 2.3.

Table 7-1: Timeout Values

AERCO Device

Parameter

Default

Value

Range

Menu

BMS II

Network Timeout

30 s

5 to 240 s

RS-232

C-More

Network Timeout

30 s

5 to 999 s

Configuration

ACS

Network Timeout

30 s

5 to 240 s

RS-232

Refer to GF-112, GF-124, and GF-131 for more information.