Appendix C:

BACNET/IP, BACNET MS/TP, METASYS N2, AND LONWORKS POINTS LIST

Appendix C.1: Four C-Mores and One ACS/BMS II/BMS

Table C-1: Four C-Mores and One ACS/BMS II/BMS

Equip

Point Name

Name

Read

Only

BACnet

Type:ID

N2 Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon Direction

ModBus/

Unit Addr.

Blr Addr 1

1

01-Fire Rate Out

boilerstate_1

AV:26

data float

1

nvoBlrState1

inc count (9) Output (non-polled)

30009/1

1

02-Active Setpoint

effectsetpt_1

AV:27

data float

2

nvoEffSetpt1

inc count (9) Output (non-polled)

30017/1

1

03-Net Remote Setpt setpt_1

AV:24

data float

3

nviSetpt1

inc count (9) Input (non-polling)

40001/1

1

05-Fire Rate In

boilerload_1

AV:28

data float

5

nvoBlrLoad1

inc count (9) Output (non-polled)

30018/1

1

06-Outlet Temp

localsuptemp_1

AV:29

data float

6

nvoLocSupTmp1 inc count (9) Output (non-polled)

30003/1

1

07-Display Code

dispcode_1

AV:22

data float

7

nvoDispCode1

inc count (9) Output (non-polled)

30001/1

1

08-Unit Status

unitstat_1

AV:23

data float

8

nvoUnitStat1

inc count (9) Output (non-polled)

30002/1

1

09-Run Cycles

runcycles_1

AV:42

data float

9

nvoRunCycles1

51

Output (non-polled)

30012-
30013/1

1

10-Run Hours

runhours_1

AV:43

data float

10

nvoRunHours1

51

Output (non-polled)

30014-
30015/1

1

11-Oxygen

o2level_1

AV:161

data float

161 nvoO2Lev1

inc count (9) Output (non-polled)

30010/1

1

12-Exhaust Temp

exhtemp_1

AV:181

data float

181 nvoExhTmp1

inc count (9) Output (non-polled)

30007/1

Blr Addr 2

2

01-Fire Rate Out

boilerstate_2

AV:30

data float

11

nvoBlrState2

inc count (9) Output (non-polled)

30009/2

2

02-Active Setpoint

effectsetpt_2

AV:46

data float

12

nvoEffSetpt2

inc count (9)

Output (non-

polled)

30017/2

2

03-Net Remote Setpt setpt_2

AV:47

data float

13

nviSetpt2

inc count (9) Input (non-polling)

40001/2

2

05-Fire Rate In

boilerload_2

AV:50

data float

15

nvoBlrLoad2

inc count (9) Output (non-polled)

30018/2

2

06-Outlet Temp

localsuptemp_2

AV:51

data float

16

nvoLocSupTmp2 inc count (9) Output (non-polled)

30003/2

2

07-Display Code

dispcode_2

AV:52

data float

17

nvoDispCode2

inc count (9) Output (non-polled)

30001/2

2

08-Unit Status

unitstat_2

AV:53

data float

18

nvoUnitStat2

inc count (9) Output (non-polled)

30002/2

2

09-Run Cycles

runcycles_2

AV:44

data float

19

nvoRunCycles2

51

Output (non-polled)

30012-
30013/2